FV-5KHz10V Frequency Voltage Converter Module 05Khz to 010V Digital to Analog Signal Module
Product information
Description
1、The module is to convert frequency pulse signal of 0-5 KHz into an analog voltage signal of 0-10V.
2、The input pulse level of 5V 12V 24V and can be directly input without string resistor. But the input signal frequency should be maintained for more than 0.5 seconds, and the output current is 5mA.
3、The converter can be used for interface conversion between PLC and inverter or interface matching control between motion control card and inverter.
4、The optical isolate is used in the input end of the signal to ensure the anti-interference ability.
5、The multi-coil potentiometer on the board is used to calibrate the corresponding relationship between frequency and voltage.
Features:
The module is to convert frequency pulse signal of 0-5 KHz into an analog voltage signal of 0-10V.
The converter can be used for interface conversion between PLC and inverter or interface matching control between motion control card and inverter.
The input pulse level of 5V 12V 24V and can be directly input without string resistor. But the input signal frequency should be maintained for more than 0.5 seconds, and the output current is 5mA.
The optical isolate is used in the input end of the signal to ensure the anti-interference ability.
The multi-coil potentiometer on the board is used to calibrate the corresponding relationship between frequency and voltage.
Specification:
Item Type:Frequency to Voltage Converter Module
Size:4.5 x 4.7 x 1.7cm / 1.77 x 1.85 x 0.67in
Relationship,Linearity:
500Hz to 1V
2.5Khz to 5V
5Khz to 10V
Package List:
1 x FV-5KHz10V Frequency to Voltage Converter Module
Note:
For use with PLC, support for NPN type. Must have a ground wire.
If you need to use an encoder, you need to keep the encoder running at a constant speed for more than 0.5 seconds.
Frequency and voltage conversion module, response time is about 0.3-0.5 seconds.
If the signal input is turbine flow, etc., due to signal matching, an 817 diaphragm and a resistor must be added to match the flowmeter to function properly.
If there is a deviation in the correspondence when using, you can adjust the blue potentiometer on the board to calibrate. At the time of shipment, we have adjusted the F/V potentiometer to a certain correspondence. It is generally not recommended to adjust it by itself.
Input power supply voltage range is 12-30 VDC, recommended supply voltage 15-24 VDC.When at 12V level, the power supply can not use 12VDC power supply, at least 15 VDC power supply, if a certain need to use 12V power supply, can also be customized 12VDC power supply converter. When at 24V level, the power supply need to use 24VDC power supply.
Features
- BrandSTUNACY
- ManoMano ReferenceME220941954
- MMID463036688079
- Product codeSTYM-GS24126
- EAN4265116049008